Hi guys
I have a problem with my Central Heating. Central Heating does not fire up when Room Stat is calling for heat. I think the problem is with my Central Heating Actuator.
Sequence is -
Heating Demand
Actuator motor rotates to "B" - open.
Boiler does not fire.
Boiler fires every time there is a HW demand.
When I look at wiring joint box I notice the Hot Water Actuator wiring and and the Central Heating Actuator wiring are linked,
Grey wire from HW Actuator and Grey wire from CH actuator are both connected.
Orange wire from HW Actuator and orange wire from CH actuator are both connected.
Is this normal.
I have a Performa 28e boiler which allows setting the control knob to either HW plus CH or
just HW.
Looks like the installation engineers thought they would just put a boiler demand on the CH input and not the HW input. IS this a regular practise?
Many thanks
Cheers
I have a problem with my Central Heating. Central Heating does not fire up when Room Stat is calling for heat. I think the problem is with my Central Heating Actuator.
Sequence is -
Heating Demand
Actuator motor rotates to "B" - open.
Boiler does not fire.
Boiler fires every time there is a HW demand.
When I look at wiring joint box I notice the Hot Water Actuator wiring and and the Central Heating Actuator wiring are linked,
Grey wire from HW Actuator and Grey wire from CH actuator are both connected.
Orange wire from HW Actuator and orange wire from CH actuator are both connected.
Is this normal.
I have a Performa 28e boiler which allows setting the control knob to either HW plus CH or
just HW.
Looks like the installation engineers thought they would just put a boiler demand on the CH input and not the HW input. IS this a regular practise?
Many thanks
Cheers