    Honeywell 3 position diverter valve clicking (V4073A1039)

    I totally recommend switching off the electrical stuff! :wink: uk-plumbing.com was where i got the replacement head from. £58 delivered and including VAT. I'm not trade so this was the cheapest i could find. I ordered at about 11am and it turned up next day via ANC/FedEx!
  2. M

    Honeywell 3 position diverter valve clicking (V4073A1039)

    Hurrah!! We are now fully operational "clicking" free!! :D Although the **** that put the valve where it is will get a reet hard slap if i ever meet him!! :lol: This evening i also learnt that 240V will give you a right good 'tickle' if your not paying attention... :oops:
  3. M

    Honeywell 3 position diverter valve clicking (V4073A1039)

    No problem, should be here today or tomorrow.
  4. M

    Honeywell 3 position diverter valve clicking (V4073A1039)

    Got one for 58GBP delivered so will wait and see if this fixes it. Thanks again!
  5. M

    Honeywell 3 position diverter valve clicking (V4073A1039)

    Not convinced my voltage measuring techniques are quite according to the text books so time to get in a proffesional. As far as i can tell from the diagram and the assortment of wires in the control box they all match up correctly. Coupled with the fault only starting late last year and we've...
  6. M

    Honeywell 3 position diverter valve clicking (V4073A1039)

    Thanks for that info. Problem is it never gets to a static mid position. Whenever it goes to the mid point the clickings starts. Will check the voltages as you suggest later.
  7. M

    Honeywell 3 position diverter valve clicking (V4073A1039)

    Checked the connections and some voltages today and found the following - Only in the "down" position for CH only - ~230V going to grey wire at this point. Then turn the thermostat on the HW and the valve moves to the mid point where it stalls and starts clicking. At this point the...
  8. M

    Hot water feed for power shower pump

    Pump fitted today and all working ok so far!! Thanks again. :D
  9. M

    Honeywell 3 position diverter valve clicking (V4073A1039)

    Thanks for the tips. Will take a look over the weekend hopefully! Any idea what sort of money is involved in the spare parts or the whole valve?
  10. M

    Honeywell 3 position diverter valve clicking (V4073A1039)

    Howdy again, Seems it's all falling apart at once in my plumbing system! When the boiler is running the 3 position diverter valve has started "clicking". The clicking noise is the microswitch being hit then the valve moving off it and then moving back and making contact with the switch...
  11. M

    Hot water feed for power shower pump

    Thanks for the feedback. I'll just stick with the current setup i think. It's worked for the best part of ten years so far!!
  12. M

    Hot water feed for power shower pump

    Thanks for the swift response. I guess the risk of not doing it per the installation manual is that it would invalidate any sort of warranty/gaurantee?
  13. M

    Hot water feed for power shower pump

    Howdy, I have a query about the hot water feed for a power shower pump. Over the festive period the pump we currently have decided that it has had enough and leaked all over the airing cupboard floor, which was nice. The leak is terminal and so i have bought a replacement pump which i'm...