A borrowed neutral is where something (nearly always a light) has its live connection on one circuit and its neutral on another:

:electrics:safety_information:borrowedneutral18be.jpg

This is most commonly encountered with 2-way switching of a landing light. The live originates on the downstairs lighting circuit and goes through the downstairs and upstairs switches to the landing light, where of course a neutral is also needed, and the easiest place to get one is from the upstairs lighting circuit. It was done like this for years, with never a problem because people only had 1 lighting circuit. The problem arises when the lighting is split into two - Upstairs & Downstairs.

The reason it's a problem is shown below. Consider the two circuits as before, and you want to break into Circuit 2 at point X to install a new light. So you switch off the MCB, or pull the fuse, verify that the circuit is dead, and cut the cable. At that point some or all of the neutral cable in Circuit 2 becomes live via the path through the light from Circuit 1.

I submit that this is a Bad Thing™

Related forum topics

No forum comments / questions currently relate to this article.


Add a comment or question about
this article in the forum:

 
Your comment or question:
First,
Existing users click here to log in.
New users click here to join FREE!
Then,
 Subject:
 Comment:

 
electrics/safety_information/sneutral.txt · Last modified: 2007/09/12 09:18 (external edit)
 
 
DIYnot.com
Find an Expert | Find a Supplier | Search DIYnot.com
My DIYnot | Advertising | Newsletter
DIYnot.com | How to... | @home | Wiki | Forum | Shop
By using this site you agree to our Terms of Service / Disclaimer.
Please read our Privacy Policy.

Copyright © 2000-2008 DIYnot Limited. All rights reserved. Reproduction in whole or in part in any form or medium without express written permission of DIYnot Limited is prohibited.