landlords gas check legal requirements

a landlord MUST confirm all pipework in the property is safe, the EASIEST way to confirm this is to do a tightness test so it has become a (good) habit, not sure how else we can confirm it is safe but could be one for the lawyers to argue about the phrase "must a tightness test be done"

your a spoil sport.
 
Sponsored Links
A friend of mine had a LLC done and the meter was locked in the garage (under my instruction as I wanted to set up the coucil contractors). The engineer didnt even ask to enter the garage - and I had loosened the inlet test pressure nipple on the boilers gas valve.

Needless to say he is now sacked!

Paul

Paul,
could you tell me the name of the coucil (council?) contractors please.

if you don`t want to post on forum could you pm me please

it may be helpful in an ongoing legal matter that my brother is involved in concerning contractors.

cheers mate.
 
Sponsored Links
A friend of mine had a LLC done and the meter was locked in the garage (under my instruction as I wanted to set up the coucil contractors). The engineer didnt even ask to enter the garage - and I had loosened the inlet test pressure nipple on the boilers gas valve.

Needless to say he is now sacked!

Paul

Paul,
could you tell me the name of the coucil (council?) contractors please.

if you don`t want to post on forum could you pm me please

it may be helpful in an ongoing legal matter that my brother is involved in concerning contractors.

if you dont mind including me in finding out who is involved i would be grateful as there are a few things going on at the moment i would like to see who is doing what so if you find out PM me as well please, i wont post any details as such which would compromise your brothers position
cheers

cheers mate.
 
It takes about 6 mins to do a Tightness Test, You are signing a CP12 to say that all is well...Could be the best 6 mins you ever spend

I do sleep well at night! ;)
 
see i thought it took 4 mins for proper test ;)

1 min let by test, 1 min stabilization and 2 min test
 
i now know why Agile likes these things discussed in combustion chamber .
We have people leaving uncontrolled leaks, people who think it is ok to leave uncontrolled leaks people who dont even know what is required on how to fill a form in and people who dont even know how to do a tightness test... Thank fek only some of you have replied.
 
see i thought it took 4 mins for proper test ;)

1 min let by test, 1 min stabilization and 2 min test

it must take slightly longer than 4 mins to do all the tests as you have to reduce pressure to 10mb for let by, raise it to 20mb for temp stability, then seal test point when finished ;) ;)
 
i know its not right but in the gas installer mag issue 162. it does actually say its not a legal requirement.under reg 36 :confused: new one on me.needless to say you,ve always gotta cover your arse.
 