Potterton FF80 Fanned Balance Flue Boiler not firing up

Joined
10 Oct 2011
Messages
11
Reaction score
0
Location
Essex
Country
United Kingdom
I have a Potterton FF80 Fanned Balance Flue Gas Fired Boiler, about 10 years old. Although the boiler will fire up when hot water is called for, it will not fire up when Central heating is called for.
I have changed the Electronic Controller, checked the Thermostat and tried a new programmer. No success. Any ideas please?
 
Sponsored Links
If got a 3 port, if on heating only should have 240v on white and grey, if so check voltage to syncron motor, may just need new motor
 
Sponsored Links
It is a two port Honeywell V4043H Motorised Zone Valve. 240volt. I aim to replace the motor
 