Hello guys... i've got a glow worm boiler Flexicom 30 cx.
It works fine as I programmed it.

I set the system to keep the house heat not to go below 18 for the afternoon period. But sometimes it feels cold so I need to override the system.

I have the wireless controller Climapro RF, I do the override by pressing the up arrow button. it asks for what temp i want and till when.

I set them and see the display shows a note of override but the boiler doesn't respond and doesn't fire up.

I even took the controller and put it near the boiler but it didn't work.

Any ideas?
 
Sponsored Links
if its a climapro 2 then you need to change the date back to anything other than 2012 and it will work as normal, it has a software issue that appeared when the year turned. let glowworm know and they will come and change it when they find a fix.
 
if its a climapro 2 then you need to change the date back to anything other than 2012 and it will work as normal, it has a software issue that appeared when the year turned. let glowworm know and they will come and change it when they find a fix.

Thanks a lot mate... I took the date back to 2011 and it worked...

many thanks :)
 
Sponsored Links
This has been bugging me for weeks, kept thinking that the Climapro 2 was on its way out! Changed it back to 2011 and its fine.

Its like the millennium bug all over again. Thanks a lot! :D
 