Extractor Fan Isolator Switch????

However, given that we're talking a bathroom, the light switch is likely to be a pull one. One might therefore end up having to use a 45/50A one designed as a shower isolator (are they OK with frequent operatiom?), since I doubt one would easily (if at all) be able to find any other type of DP pull-switch.

Legrand 061130 is a 16A DP pull-cord. Or MK switch + base

http://www.tlc-direct.co.uk/Products/MK3151.html
http://www.tlc-direct.co.uk/Products/MK2051.html

Really there is an opportunity for an enterprising manufacturer to produce a 3-pole isolator with a fuse!
 
Sponsored Links
Yep, at least qualitatively (the bathroom environment may make faults a bit more common) ... but would not the manufactuer's instructions for that 'fan/light' also quite probably call for an all-pole isolator?

Kind Regards, John


I wasn't implying that either type of fan did/didn't require a seperate isolator - I was commenting on the reasons that Bernard gave for this seperate isolator.


I was also commenting on what you termed 'true isolation'.........ironically, a spark can get the DNO in to pull the main fuse so that he can do a CU swap on an installation - but an extractor fan needs 3-pole isolation??? :)
 
How's that ironic? How else will you do a CU change without working live?
 
How's that ironic? How else will you do a CU change without working live?

The irony is in the fact that they are only isolating the 'Line' conductor by pulling the fuse - not the 'neutral'.......was I not clear?? :).......yet you need 3-pole isolation to work on a fan.
 
Sponsored Links
Fitting an isolator to a fan seems to have beome more of a habit than anything. My fan instructions don't ask for a 3A fuse or an isolator but I'll probably fit an isolator anyway. Won't bother with fuse though - too difficult.
 
I wasn't implying that either type of fan did/didn't require a seperate isolator - I was commenting on the reasons that Bernard gave for this seperate isolator.
Fair enough, but "Bernard's reason" (which has been cited by a good few others in the past) applies in both cases, doesn't it?
I was also commenting on what you termed 'true isolation'.........ironically, a spark can get the DNO in to pull the main fuse so that he can do a CU swap on an installation - but an extractor fan needs 3-pole isolation??? :)
Yes, that is ironical, particularly in a TT installation, in which case the regs would not regard it as 'adequate isolation'. I was wrong/careless when I used the term "true isolation". What I meant, and should have written, was "all-pole isolation" (i.e. 'true isolation' in a literal everyday sense) - since (per the 'Bernard reason') that is what is required to isolate a N-E fault.

Kind Regards, John
 
Fitting an isolator to a fan seems to have beome more of a habit than anything. My fan instructions don't ask for a 3A fuse or an isolator ...
In my experience, that's unusual these days.

Lest anyone think otherwise, I should perhaps say that I'm one of those people who doesn't really see any great point/need in singling out fans for a requirement for individual all-pole isolation (which, of course, the regs themselves do not do). Similar arguments could be applied to all sorts of other things and, although that might offer a few advantages, we generally cope quite satisfactorily without everything having separate isolators (even if it involves inconvenience, like the need for some temporary lighting during repair work etc.). However, many/most manufacturers do call for fan isolators - so those who are constrained to work to the letter of BS7671 have no real choice but to comply with that "manufacturer's instruction".

Kind Regards, John
 
I wasn't implying that either type of fan did/didn't require a seperate isolator - I was commenting on the reasons that Bernard gave for this seperate isolator.
Fair enough, but "Bernard's reason" (which has been cited by a good few others in the past) applies in both cases, doesn't it?

Kind Regards, John

I have only ever fitted one of these ceiling fan/lights, although I have come across a few, (both my mother and mother in law have them), but I have yet to come across one with it's own, seperate isolator.

They utilise the existing lighting circuit via the existing light switch and you run a second switch drop if you want seperate control of the fan.

So what happens if, as Bernard says, :-

.....the fan comes defective or a hazard and HAS to be isolated then without a 3 pole isolator the only way to remove the hazard is to turn off the lighting circuit at the CU. Do you want ( can you allow ) your tenants to live in a house with no lights until the fan is repaired.



You switch it off at the light switch and call an electrician........as you would with the bathroom fan. :)
 
OwainDIYer";p="2650741 said:
Really there is an opportunity for an enterprising manufacturer to produce a 3-pole isolator with a fuse!

Had a brainwave and there is a (Click Scolmore) grid solution for that!! :D :D

mini grid 3 pole isolator http://www.astra247.com/8164/Electr...le-Fan-Isolation-Lockable-Switch/Polar-White/

plus a mini grid fuse module http://www.astra247.com/7147/Electrical/Mini-Grid-13A-Fused-Spur-Module/Polar-White/

All in a suitable plate. Job done.

Also I see that the 3 pole isolator is lockable. Don't know if it is lockable in the ON position though.........
 
I have only ever fitted one of these ceiling fan/lights, although I have come across a few, (both my mother and mother in law have them), but I have yet to come across one with it's own, seperate isolator. They utilise the existing lighting circuit via the existing light switch and you run a second switch drop if you want seperate control of the fan. So what happens if, as Bernard says, :-
.....the fan comes defective or a hazard and HAS to be isolated then without a 3 pole isolator the only way to remove the hazard is to turn off the lighting circuit at the CU. Do you want ( can you allow ) your tenants to live in a house with no lights until the fan is repaired.
You switch it off at the light switch and call an electrician........as you would with the bathroom fan. :)
I don't quite understand your point - am I talking myself into confusion? :). In the case of a ceiling fan+light, switching it off at the light switch (2 switches, if fan is switched separately) will remove all L feeds from the fan+light - therefore safe whilst one waits for the electrician to turn up (the worst posible issue, nuisance but not unsafe, being a persisting RCD trip if there is a N-E fault). The issue with extractor fans relates only to 'timer' ones (because they have a 'permanent L' feed) - which creates a different situation to that with the ceiling fan+light. If smoke or flames (or frighening noises) starts coming out of one of those, almost certainly fuelled by the 'permanent L', switching off the light switch will do nothing, and only switching the circuit off at a CU (if there is no 'fan isolator') will make things safe whilst awaiting the electrician.

Kind Regards, John
 
Really there is an opportunity for an enterprising manufacturer to produce a 3-pole isolator with a fuse!
It were actually OwainDIYer, not me, but ...
Had a brainwave and there is a grid solution for that!! :D :D
mini grid 3 pole isolator ... plus a mini grid fuse module ... All in a suitable plate. Job done. Also I see that the 3 pole isolator is lockable. Don't know if it is lockable in the ON position though.........
Clever idea. If you were simply putting that in the feed to to the fan, you might have to up that to two fuse modules, if you believed that the MIs were calling for both L and S/L feeds to be fuse-protected.

Kind Regards, John
 
....so those who are constrained to work to the letter of BS7671 have no real choice but to comply with that "manufacturer's instruction".

Kind Regards, John


Yes, annoying, isn't it?

You go over the top with the cooker circuit in your new kitchen, just in case - you run a 10mm cable on a 50 Amp MCB.

You pop out with the missus to choose your nice new cooker and when it arrives the instructions tell you you should only connect to a 40 Amp, 6mm circuit.

You're not ripping the 10mm out and yet you're not complying with the manufacturers instructions.

By not complying with manufacturers instructions you're not complying with BS7671, so you can't sign off your EIC.

Great, aren't they - manufacturers can request any old twaddle that they like, probably without having a clue about electrics in the first place, and you can't question it or do what you think is better because of a couple of lines in BS7671.
 
Clever idea. If you were simply putting that in the feed to to the fan, you might have to up that to two fuse modules, if you believed that the MIs were calling for both L and S/L feeds to be fuse-protected.

Kind Regards, John

If I were wiring it, I would bring the lighting feed into the fan isolator grid fuse first. That's the permanent live to the isolator switch. From this point the live also feeds the bathroom light switch.
The switched live is on the return leg and that goes to the L2 contact on the isolator switch.
That way the live and switched live are both fused, with one fuse. Voila!
 

DIYnot Local

Staff member

If you need to find a tradesperson to get your job done, please try our local search below, or if you are doing it yourself you can find suppliers local to you.

Select the supplier or trade you require, enter your location to begin your search.


Are you a trade or supplier? You can create your listing free at DIYnot Local

 
Sponsored Links
Back
Top