its Been in empty house for a month or two.Now lights on both heat and hot water but trips out .Spark continues while burner lit until trip out after approx. 5 to 10 seconds. .
 
Sponsored Links
Pre payment gas meter, money on card ? Gas turned off, disconnected ?

Someone turned the gas isolator off under boiler ?
 
all is fine,its firing then not rectifying then tripping.Reset,same again. Theres continuity rfom probe to board
 
Sponsored Links
maybe, I think its a board problem.Probably been damp lying there unused for a while.I was wondering if it could be the condensation sensor but im sure if it was the boiler wouldn't fire at all
 
Came across a similar instance once, where the polarity had been reversed by some idiot putting the leccy on the fiddle.
 
Came across a similar instance once, where the polarity had been reversed by some idiot putting the leccy on the fiddle.

That's quite common when you have no ionisation.
Of course if you're thinking of going into the burner combustion chamber you'll need to be a Gas Safe RGI & have a set of replacement seals.
 