Hi,

I've the Danfoss TP5000-RF with these settings for the heating to turn on only at 22:30 till 01:00,

1. 06:30
2. 06:30
3. 11:30
4. 11:30
5. 22:30 24°C
6. 01:00 OFF

The settings has been working since I got it installed few months ago but the past few days, the heating would automatically turn on outside the times I have set and the only way to turn it off is to hold the up and down arrow which puts it in frost protection mode.
 
Sponsored Links
What temperatures have you set for the first four events?

If you want the heating to stay off, set a low temperature for 1 to 4. 12C for each would do it.
 
Does the red light go out after 1.00 am?
When you raise and lower the demand temperture, does the green flash?
 
Sponsored Links
What temperatures have you set for the first four events?

If you want the heating to stay off, set a low temperature for 1 to 4. 12C for each would do it.
The first four events temperatures are default so event 1 and 3 is 20°C and 2 and 4 is 15°C

I've set 10°C for the first four events and it seems to solved it! However was wondering what does it mean?

Does the red light go out after 1.00 am?
When you raise and lower the demand temperture, does the green flash?
Yes, the red light turns off after 1AM and the heating stops
 