Installing and Wiring a Potterton PTT2 Cylinder Thermostat

Joined
4 Jul 2012
Messages
3
Reaction score
0
Location
Southampton
Country
United Kingdom
Faced with this problem I found lots of confusing and incomplete information on various sites.

So this note gives the benefit of my experience in getting this cylinder stat working.

Most commonly people will be replacing a bi metal mechanical thermostat which sits on the cylinder with this electronic, remotely controlled stat.

The PTT2 has a much more sensitive response than most bi metal stats. Typically the PTT2 will cut out at the temperature you set and cut back in when the temperature falls by 5 or 6 degrees centigrade. A bi metal stat will need a much bigger temperature drop before it cuts back in.

So if you set a low temperature (say 45 to 50 degrees) to save fuel then with a bi metal stat the water will run cold before it has time to be reheated. To avoid this problem with a bi metal stat you will need to set a higher temperature (60 degrees plus) and you will use/waste more energy.

The PTT2 avoids this problem.

The PTT2 has five connections. This means you will need to run a 2 core and earth wire (Brown, Blue, Earth) plus a three core and earth wire (Red, Blue, Yellow, Earth) to the stat. To distinguish the two blue wires, strip one wire back at each end and sleeve it in red (say).

The lead from the sensor to the stat can be fed into the stat on the surface or from the rear if the stat is mounted on a 25mm box.

The sensor can be strapped to the HW cylinder or if the cylinder has the foam moulded to it, cut a hole slightly bigger than the sensor, push the sensor against the cylinder, fill round with foam insulation cut from pipe insulation, push down and seal over with brown parcel tape!

The PTT2 fitting instructions are at the end of this note.

Now for the wiring.

The PTT2 terminals are labelled 1 to 5 (left to right), connections are

Terminal Symbol Function Wire Connect to
1 H HW On/Call Blue with sleeve Terminal 8
2 C HW Off/Satisfied Yellow Terminal 7
3 L Permanent Live Red Terminal 1
4 TL HW on Call from Programmer/Timer Brown Terminal 6
5 N Permanent Neutral Blue Terminal 2

At the Stat both earth wires should be sleeved and connected to the earth terminal in the 25mm box. In the Wiring Centre both earth wires should be sleeved and connected to Terminal 3.

The Connect to Terminal Numbers are those in the standard Y plan Wiring Centre with a mid position valve. These are shown in the diagram below.

If you have a different Wiring Centre set up, then you can deduce the correct terminals by choosing

Blue with sleeve (H) connects to the terminal which connects via the orange (usually) wire to the mid position valve.

Yellow (C) connects to the terminal which connects via the grey (usually) wire to the mid position valve.

Red (L) connects to the terminal which has a wire running to the live on the fused connection unit supplying power to the boiler.

Brown (TL) connects to the terminal which has a wire connecting to the HW Call terminal on the programmer/timer.

Blue (N) connects to the terminal which has a wire running to the neutral on the fused connection unit supplying power to the boiler.

How it works

If timer is switched on for water heating then if the temperature not satisfied the water will heat (green light on Stat) until it is hot enough (red light on Stat). If the water temperature falls (say through use) cycle will repeat.

If timer is not switched on for water heating, no lights will show.

If timer is switched on for water heating the boost button has no effect – as it should because either the water is hot enough or it is already heating!

If timer is not switched on for water heating and you push the boost button, yellow and green lights will show and a tank of water will be heated at which point the red light will show.


 
Sponsored Links
Yes - UK recommendations particularly for non domestic buildings are for 60 degrees.

However in North America (and perhaps elsewhere) the recommended temperature is 49 degrees. Regulations state

WHILE THERE IS A VERY SLIGHT RISK OF PROMOTING LEGIONELLAE BACTERIA WHEN HOT WATER TANKS ARE MAINTAINED AT 49 (120 F) DEGREES, THIS LEVEL IS STILL CONSIDERED SAFE FOR THE MAJORITY OF THE POPULATION. IF YOU HAVE A SUPPRESSED IMMUNE SYSTEM OR CHRONIC RESPIRATORY DISEASE, YOU MAY CONSIDER KEEPING YOUR HOT WATER TANK AT 60 (140 F) DEGREES. HOWEVER, THIS HIGH TEMPERATURE SIGNIFICANTLY INCREASES THE RISK OF SCALDING. (Sorry regulations are printed in UC).

Reducing the temperature will save about 8% on your water heating bills.
 
Sponsored Links
Here is an update which explains how to incorporate a changeover relay so as to ensure that the thermostat operates as intended with a 'standard' mid-position valve.

Installing a Potterton PTT2 Cylinder Thermostat


Faced with this problem I found lots of confusing and incomplete information on various sites.

So this note gives the benefit of my experience in getting this cylinder stat working.

Most commonly people will be replacing a bi metal mechanical thermostat which sits on the cylinder with this electronic, remotely controlled stat.

The PTT2 has a much more sensitive response than most bi metal stats. Typically the PTT2 will cut out at the temperature you set and cut back in when the temperature falls by 5 or 6 degrees centigrade. A bi metal stat will need a much bigger temperature drop before it cuts back in.

So if you set a low temperature (say 45 to 50 degrees) to save fuel then with a bi metal stat the water will run cold before it has time to be reheated. To avoid this problem with a bi metal stat you will need to set a higher temperature (60 degrees plus) and you will use/waste more energy.

The PTT2 avoids this problem.

The PTT2 has five connections. This means you will need to run a 2 core and earth wire (Brown, Blue, Earth) plus a three core and earth wire (Red, Blue, Yellow, Earth) to the stat. To distinguish the two blue wires, strip one wire back at each end and sleeve it in red (say).

The lead from the sensor to the stat can be fed into the stat on the surface or from the rear if the stat is mounted on a 25mm box.

The sensor can be strapped to the HW cylinder or if the cylinder has the foam moulded to it, cut a hole slightly bigger than the sensor, push the sensor against the cylinder, fill round with foam insulation cut from pipe insulation, push down and seal over with brown parcel tape!

The PTT2 fitting instructions are at the end of this note.

Now for the wiring.

The PTT2 terminals are labelled 1 to 5 (left to right), connections are

Terminal Symbol Function Wire Connect to
1 H HW On/Call Blue with sleeve Terminal 8
2 C HW Off/Satisfied Yellow Terminal 7
3 L Permanent Live Red Terminal 1
4 TL HW on Call from Programmer/Timer Brown Terminal 6
5 N Permanent Neutral Blue Terminal 2

At the Stat both earth wires should be sleeved and connected to the earth terminal in the 25mm box. In the Wiring Centre both earth wires should be sleeved and connected to Terminal 3.

The Connect to Terminal Numbers are those in the standard Y plan Wiring Centre with a mid position valve. These are shown in the diagram below.

If you have a different Wiring Centre set up, then you can deduce the correct terminals by choosing

Blue with sleeve (H) connects to the terminal which connects via the orange (usually) wire to the mid position valve.

Yellow (C) connects to the terminal which connects via the grey (usually) wire to the mid position valve.

Red (L) connects to the terminal which has a wire running to the live on the fused connection unit supplying power to the boiler.

Brown (TL) connects to the terminal which has a wire connecting to the HW Call terminal on the programmer/timer.

Blue (N) connects to the terminal which has a wire running to the neutral on the fused connection unit supplying power to the boiler.

Now for the Unfortunate Twist

The thermostat will not create the correct switching through the mid-position valve when the boost button is pushed.

This is hinted at in a review on heating controlsonline.co.uk which says ‘Not suitable for mid position valve without adding a changeover relay’.

If the system has CHon and HWoff then the valve is ‘fully over’ and the grey valve wire is +ve.

If the boost button is pushed then the boiler will fire but the +ve grey wire will ensure that the valve cannot return to its mid position. No HW will be heated, there will only be CH heat.

This is not the result we require.

Pushing the boost needs to switch off the +ve grey wire, allowing the valve to return to its mid position and provide both HW and CH.

If the system has CHoff and HWoff then the valve is ‘fully rewound’ and the valve has no +ve connection.

If the boost button is pushed then the boiler will fire and the valve will stay in its ‘fully rewound’ position because it is not receiving any power. HW will be heated, but (as expected) there will be no CH heat.

This is the result we require.

Using a Relay

The relay needs to achieve the required result: Pushing the boost needs to switch off the +ve grey wire.

An A4810 like this will do the trick:

http://www.amazon.co.uk/MGR-1-A4810-Single-Phase-Solid/dp/B00WJD4B2E

This is widely available for about £7.

The required connections are:

PTT2 Terminal C to A4810 control terminal, A4810 control terminal to Terminal 7 in the standard Y plan Wiring Centre. This is AC so the A4810 terminals can be used either way round.

Programmer HWoff Terminal to A4810 output terminal Terminal 7 in the standard Y plan Wiring Centre to A4810 output terminal. This is AC so the A4810 terminals can be used either way round.

How it works

If the programmer is switched on for water heating then if the temperature not satisfied the water will heat (green light on Stat) until it is hot enough (red light on Stat). If the water temperature falls (say through use) cycle will repeat (while the programmer is calling for HW).

If the programmer is not switched on for water heating, no lights will show.

If the programmer is switched on for water heating the boost button has no effect – as it should because either the water is hot enough or it is already heating!

If the programmer is not switched on for water heating and you push the boost button, yellow light (on the boost button) and green light will show and a tank of water will be heated at which point the red light only will show.
 