Having a nightmare

Status
Not open for further replies.
Joined
4 Sep 2019
Messages
350
Reaction score
214
Location
Glasgow
Country
United Kingdom
Been or this job 7 days. Just filled and fired up 2 x 40cdi greenstar regulars. Gas rated them together - getting 72kW @ max. However only getting 5mb working pressure at either boiler. 21mb at meter. Spoke to Worcester and Gas Safe and they're as baffled as I am (although Gas Safe tech said they'll get back to me). Cannot get my head around the gas rate being so high when wp so far off. Anyone any ideas?
 
Sponsored Links
Got a few boys coming over tomorrow, we'll try a few things. Getting 20mb when set to low. Gas Safe tech help said he'd heard the same problem last week and they didn't get to the bottom of it.
 
Sponsored Links
Was black dust. Spoke to two Gas Safe tech helps today and they didn't have a definitive answer re gas rate. Blockage on the P1? So MikeCip's idea with the T's would have shown it right away. So thanks for that.

Gas rated separately 1st. Then together. Don't think the way I communicated the volume of gas used mattered to much in this instance, kW, cubic ft/m. Point was I was surprised that 5mb wp was achieving it. Although looks like this was a false reading (blockage at P1)

Cheers guys.
 

DIYnot Local

Staff member

If you need to find a tradesperson to get your job done, please try our local search below, or if you are doing it yourself you can find suppliers local to you.

Select the supplier or trade you require, enter your location to begin your search.


Are you a trade or supplier? You can create your listing free at DIYnot Local

 
Status
Not open for further replies.
Back
Top