I have no exit tones from the indoor speaker when setting area b
And how do I change text for part set in area a
I have changed the full unset banner ok and the banner for area b set ok
Thank you in anticipation
 
Sponsored Links
Enable speaker for area b.....area options
Text in global text
 
Last edited:
Sponsored Links
13A4EAD4-3893-4BAE-BA9A-ACA2EC8221CA.jpeg
 
Thank you again sparkymarka for your kind responce.
I have doubled checked the settings with the manual all the sounder options are on as in the list, I have followed the flow chart through on page 81 its programmed exp *1,1 areas AB vol is at level 4
The speaker DOES sound if there is an alarm in area b but not in exit, also there is no audio from panel internal buzzer or from keypad.
In area A all sounds are normal
Its a brand new panel and it did sound correctly when I first commissioned it but I defaulted it then this problem began.
Just in case I did something odd I defaulted again this morning and recommissioned again but no improvement.
I have not changed any wiring ect its all as it was.
 
Have now cracked it, it was pointed out to me by a Texecom Tech expert to check the area address setting of the keypad.
Doing this I discovered that it was only programmed to A adding B solved the problem.
 