Hi everyone, first time posting, so go easy!!
I’m opening up my existing fireplace and am looking for guidance re the lintels.
My existing opening is 1000mm and we’re opening it up to 1500, so my lintels will be 1900 ish.
The external wall is flush outside and the chimney breast sits inside the kitchen wall in an alcove.
The alcove is about 400mm deep, three bricks thick - the first of which has the existing builders arch and will be the final finished wall, the internal two make up the sides of the inside of the chimney.
There’s a loft conversion bedroom above, no other chimney, then the gable end of the slate roof.
I was planning on using two bits of 2x4 nailed together (or some 6x4 sleepers - no money left, so using what I have!!) as my needles with timbers/props underneath them on both sides, inside & outside the house.
I wasn’t sure if strongboys would adequately support the middle row of brick?
Do you reckon I’m best supporting from both sides, or would it be okay supported internally only?
I’m going to fit two lintels, one at the front and one against the back wall, but am now wondering if I need a third for the middle course of brick?
Last silly question, can I leave the needles in once the lintels are in place? I’d be mortaring them in place as much as I could.
I’ve hopefully attached some pictures
Thanks in advance
I’m opening up my existing fireplace and am looking for guidance re the lintels.
My existing opening is 1000mm and we’re opening it up to 1500, so my lintels will be 1900 ish.
The external wall is flush outside and the chimney breast sits inside the kitchen wall in an alcove.
The alcove is about 400mm deep, three bricks thick - the first of which has the existing builders arch and will be the final finished wall, the internal two make up the sides of the inside of the chimney.
There’s a loft conversion bedroom above, no other chimney, then the gable end of the slate roof.
I was planning on using two bits of 2x4 nailed together (or some 6x4 sleepers - no money left, so using what I have!!) as my needles with timbers/props underneath them on both sides, inside & outside the house.
I wasn’t sure if strongboys would adequately support the middle row of brick?
Do you reckon I’m best supporting from both sides, or would it be okay supported internally only?
I’m going to fit two lintels, one at the front and one against the back wall, but am now wondering if I need a third for the middle course of brick?
Last silly question, can I leave the needles in once the lintels are in place? I’d be mortaring them in place as much as I could.
I’ve hopefully attached some pictures
Thanks in advance