Currently doing a new downstairs toilet, but moving the toilet to a new location. The old toilet outlet is about 180mm from the floor, which goes pretty much horizontally into the soil pipe, which is roughly 30cm from the toilet. The new toilet will be around 2-3m away from this location (haven't decided yet). My calculations suggest the minimum fall on 2m should be 2cm total drop, so this will basically put the outlet of the soil pipe 2cm higher than the toilet outlet. I would prefer the toilet in another location, this will be about 3m away, this will require a 3cm drop?
I cant lower the branch connection on the stack at all (I dont think - its in concrete, can provide a pic if necessary?)
What options have i got here? I am hoping i cant get away with a 20mm offset toilet pan connector, rather than putting the toilet on a plinth. Will this work? Failing that i guess i can get a wall hung toilet? If i go for the 3m run, 3cm drop, can i use a 40mm offset connection, then increse drop to 4cm?
Thanks
I cant lower the branch connection on the stack at all (I dont think - its in concrete, can provide a pic if necessary?)
What options have i got here? I am hoping i cant get away with a 20mm offset toilet pan connector, rather than putting the toilet on a plinth. Will this work? Failing that i guess i can get a wall hung toilet? If i go for the 3m run, 3cm drop, can i use a 40mm offset connection, then increse drop to 4cm?