accenta mini alarm

Joined
17 Dec 2020
Messages
5
Reaction score
0
Country
United Kingdom
hi guy's, i'm a spark to trade so don't know much about alarms, i'm doing a bench test on the above alarm before fitting and have come across a problem ,when i use the user code then press p then program 2 everything works as it should, when i disconnect 1 of the zones that is inhibited the alarm sounds, if i use the omit button then press the zones i require everything works even when i remove the links, why does the alarm sound when i remove the links in the inhibited setting. thanks in advance
 
Sponsored Links
Sounds like not programmed correctly.
Default panel and start again.
When omit is enabled it will omit that zone selected whether it is programmed in the part set mode or not.
 
hi, thanks for your reply, could you possibly run through the sequence to program a zopne for the likes of pir's to inhibit. thanks
 
From default zone 2 is programmed as inhibit in all part set functions
Screenshot_20201217-201252.png
 
Sponsored Links
thanks, seen that, my problem is i have 2 zones with pir's and need both to be inhibited at night. i've been trying to set it up on program 2, making zones 2 and 4 inhibited.
 
As per instructions
Use the zone number to toggle off or on, press 2 and LED zone 2 should go off press again and 2 will light up again. Ensure you zone 2 and 4 led's are off and press reset 3 times to leave mode.Screenshot_20201217-203341.png
 
think i've solved the problem, when in program 2 i've turned zone 2 + 4 to unused, this seems to have worked. thanks for all your help
 