Hot Water not enabling while central heating running

Joined
29 May 2020
Messages
18
Reaction score
0
Country
United Kingdom
Hello,

Nest 3rd Gen, Hot Water cylinder, British Gas 330 rebadged Glowworm, Drayton MA1 3 way actuator and Drayton HTS3.

If both CH and HW off, Actuator sits in middle position .

Central heating turns off and on absolutely fine, manually controlling and scheduling via Nest, moving to H position.

If the CH is ON and HOT WATER is called either manually or via the Nest schedule, the Actuator will remain on H. switching the CH off results in the actual moving to W.

Manually calling the HW when off will move to W and heat the HW.

If I turn the HTS3 right down to OFF, the actuator click and will move away from W. I am wondering if everything is behaving normally as I am sure it used to start to heat the water when scheduled
And the CH was on.

One thing I have noticed is that the HW can be absolutely roasting and it doesn’t seem to do anything to stop heating the water.

Thanks for any help.
 
Sponsored Links
It appears to have been mis-wired.
Is the Nest newly installed?
Which port (port letter cast into the 3-port valve body) goes to the hot water cylinder?

As always, some photos would answer many questions of this type.
 
sounds like you havent wired the HW off wire and the satisfied wire from the cyl stat in properly
 
It appears to have been mis-wired.
Is the Nest newly installed?
Which port (port letter cast into the 3-port valve body) goes to the hot water cylinder?

As always, some photos would answer many questions of this type.

The Nest was installed about 4 - 5 years ago by an “electrician” arranged by First Utility. He brought his “tools” in a single use Tesco carrier bag. Demonstrated the system “working” and then left. I realized later that the heating and hot water were wired back to front. After trying to get a return visit to sort it out, I ended up correcting it in such a way that it worked correctly to give us heat and hot water but to be honest, we have tended to demand the hot water as have hardly been in the house during previous years when it would need to be on a schedule like we need it now.

I can tell you that the wiring box beside the hot water cylinder and actuator has the following cables connected:

# / ACTUATOR CABLE / HTS3 CABLE
2 / BLUE / -
5 / WHITE / -
6 / - / BROWN
7 / ORANGE / BLACK
8 / GREY / BLUE
 
Sponsored Links
Here’s a picture of the Nest Heat Link
 

Attachments

  • 3C3FE39A-E28F-4F5F-89B6-09F7DCAAC79D.jpeg
    3C3FE39A-E28F-4F5F-89B6-09F7DCAAC79D.jpeg
    183.8 KB · Views: 67
you will have a wiring centre probably what the motorised valve wires into, can you post a pic of the wiring in there
 
Do these help?

19794484-150F-499D-A786-00C747AF651C.jpeg
 

Attachments

  • 9F7B715B-C56A-490D-B861-8AE8150B719E.jpeg
    9F7B715B-C56A-490D-B861-8AE8150B719E.jpeg
    354.2 KB · Views: 62
  • 830A1C7E-F517-4FF9-B668-11E0EB4E2A15.jpeg
    830A1C7E-F517-4FF9-B668-11E0EB4E2A15.jpeg
    419.2 KB · Views: 58
Wow! That will engage Ian.

If he was at your place then he might suddenly get a call to say his wife was having a baby and he had to rush off!

Others might post a photo of what a proper Wiring Center looks like!
 
o_O I hope so...! This is how I believe the installation has been since the house was built... we have had it for about 7 years.

it’s an ex showhouse from the 90s but you wouldn’t think it with the amount of things I’ve had to sort out. I believe the boiler itself was replaced in 2010.
 

DIYnot Local

Staff member

If you need to find a tradesperson to get your job done, please try our local search below, or if you are doing it yourself you can find suppliers local to you.

Select the supplier or trade you require, enter your location to begin your search.


Are you a trade or supplier? You can create your listing free at DIYnot Local

 
Sponsored Links
Back
Top