Minimum fall required for foul pipe?

Joined
4 Jan 2009
Messages
459
Reaction score
5
Location
True North
Country
United Kingdom
What's the minimum fall for a foul pipe underground over a long distance like 70m? The 110mm pipe.

I know 1 in 40 is ideal. Also, is there a minimum depth the inspection chamber bottom should be from when it exits the property under building regs?
 
Sponsored Links
What's the minimum fall for a foul pipe underground over a long distance like 70m? The 110mm pipe.

I know 1 in 40 is ideal. Also, is there a minimum depth the inspection chamber bottom should be from when it exits the property under building regs?

it depends

"A foul drain taking the discharge from a minimum of one WC can be laid at 1:80 (12.5mm per metre)."
 
Out of interest... Is it true that (other than vertical downpipes) a sewer fall can be too steep, and counter-productive? Or did I dream that?
 
Out of interest... Is it true that (other than vertical downpipes) a sewer fall can be too steep, and counter-productive? Or did I dream that?
That is true, the liquid travels too fast for the err......

A back drop manhole solve that.
 
Sponsored Links
I need to connect to a chamber in the road 73m away for a 4 bedroom house with 3 toilets and 2 bathrooms. 1 in 40 isn't achievable because the chamber isn't 1825mm deep.
 
Too shallow a fall and the solids can be left behind, whilst the water seeps away. Too steep a fall, and the water rushes off, leaving the solids behind. As per Woody, the correct fall is required to achieve a Self Cleansing Velocity where the water will take the solids along with it.

What sort of fall can you achieve over that distance? If going with a shallower gradient it needs to be constant, and ideally a straight run. If you cant get a suitable fall from the property to the nearest gravity sewer, the only option, (aside from a Septic Tank/Treatment Plant), is to pump it.
 
@Hugh Jaleak What do you mean by constant? Apart from one 90 degree to turn around the property after 8m, the rest should almost be a straight line apart from a slight offset possibly 15 degrees. But there will have to be rodding/inspection points at the recommended distances which I need to find out.

I believe lower gradients can benefit from being laid onto a dry ready mix of sand & cement to prevent any future sagging and then surrounded with pea gravel. I think 1:100 is achievable but don't want any less and would really like to edge it towards 1:100.

As the upstairs pipe exits the rear of the property into a chamber, i could pass the pipe under the block and beam floor and out to the front in a straight line down the drive to the road but i'm not overly keen on pipes in places you can never access them again. It would save 9/10m.
 
By 'Constant' I mean it must maintain the gradient over it's entire length, no dips, rises or flat spots, or you'll soon have a problem.

Used to be a maximum of 100 metres between Manholes, not sure if that's still the case. Know of plenty of runs that are considerably more mind you!

I've never bedded on anything other than peagravel, (or concrete when a shallow run under a building.) Going under a block and beam floor will be fine, provided the pipe has been laid correctly, virtually every new house is built using this method of flooring now I think. Check with BCO to see what they'll allow.
 
As I said above, never known pipes to be laid on anything other than peagravel, and I've seen everything from 100mm house drains to 1200mm storm sewers go in the ground, even box culverts are sat on a gravel bed. Just the size of the stones gets bigger for the bigger pipework.

This is what you need to read, Drainage and waste disposal: Approved Document H - GOV.UK (www.gov.uk) Appreciate they do state shorter distances between access points, (i.e. Chambers), but if you're putting in a straight run, in the event of a blockage, any decent jetter should carry around 80metres of hose, so can get at the issue from one end or the other. Your BCO will have the final say though, speak to them and agree the spec before doing too much work!
 

DIYnot Local

Staff member

If you need to find a tradesperson to get your job done, please try our local search below, or if you are doing it yourself you can find suppliers local to you.

Select the supplier or trade you require, enter your location to begin your search.


Are you a trade or supplier? You can create your listing free at DIYnot Local

 
Sponsored Links
Back
Top