- Joined
- 20 Oct 2020
- Messages
- 109
- Reaction score
- 3
- Country
I want to fit an external flood light and was thinking about putting junction box outside on the wall to join the cable from the light to the cable from the lighting circuit.
If the junction box has "nipples" do I need to use 20mm glands?
Should I take the twin and earth cable from the circuit into the back of the box or into the bottom?
I've read it is better to have both the cable from the light and the circuit into the bottom of the box so water cannot ingress.
If the cable goes into the bottom, as I understand it T+E is not rated for external use. Do I need an external grade cable to then connect internally onto the lighting circuit T+E?
This is a separate lighting circuit for exterior lights so there is discretion if a fault develops.
Thanks in advance.
If the junction box has "nipples" do I need to use 20mm glands?
Should I take the twin and earth cable from the circuit into the back of the box or into the bottom?
I've read it is better to have both the cable from the light and the circuit into the bottom of the box so water cannot ingress.
If the cable goes into the bottom, as I understand it T+E is not rated for external use. Do I need an external grade cable to then connect internally onto the lighting circuit T+E?
This is a separate lighting circuit for exterior lights so there is discretion if a fault develops.
Thanks in advance.