Red & green twin (strange)

Come to think of it, I think the old imperial lighting wires did have three strands.
Indeed, as I said, I thing 3/0.029" was the norm for lighting.
Presumably the old switch drops would consist of two or three of these red and green cables. I don't think blacks or neutrals were brought to the switch, particularly around the 1960s as suggested.
True, I should not have mentioned black - they would probably both have been red.
As I understand it, the red is sheathed and insulated, the green in only insulated, and two are 'stuck together' sort of thing.
Fair enough - so you're suggesting that 'switch drop' consisted of two separate cables, each consisting of an insulated-and-sleeved red 'stuck to' a green-insulated CPC? ... but did lighting cables actually have CPCs at that point in history?

Kind Regards, John
 
Sponsored Links
Indeed, as I said, I thing 3/0.029" was the norm for lighting.
True, I should not have mentioned black - they would probably both have been red.
Fair enough - so you're suggesting that 'switch drop' consisted of two separate cables, each consisting of an insulated-and-sleeved red 'stuck to' a green-insulated CPC? ... but did lighting cables actually have CPCs at that point in history?

Kind Regards, John
See my previous edited post regarding the neutrals.

Typically three reds at the switch - feed in, feed out, switch live.

End of line would have two reds at the switch.

Sheathed and insulated neutrals (with no earth usually) running to the lights.

After 1966 there would have been earths, so this could be just after 1966ish.

Before 1966 it wasn't unheard of for lighting circuits to have an earth conductor in them, particularly if 5 amp sockets were used for lighting. The earth may not have been constant through the entire circuit though.
 
Last edited:
See my previous edited post regarding the neutrals. Typically three reds at the switch - feed in, feed out, switch live. End of line would have two reds at the switch. Sheathed and insulated neutrals (with no earth usually) running to the lights.
Thanks for clarifying
After 1966 there would have been earths, so this could be just after 1966ish. .... Before 1966 it wasn't unheard of for lighting circuits to have an earth conductor in them, particularly if 5 amp sockets were used for lighting. The earth may not have been constant through the entire circuit though.
Indeed. In some of the ancient (certainly pre-1960s) bits of wiring I inherited in my house (but not still in-service by then!), it seems that at least some parts of some of the lighting circuits had 'earths' (for whatever reason). L, S/L and N were generally VIR singles, but often with a separate totally bare 'earth' running alongside. Mind you, it seems that the 'power' circuits also had a similar bare separate 'earth'.

Kind Regards, John
 
Sponsored Links
In the 50s properties sometimes had their lighting wired in the early pvc T+E, and the bare earths were simply twisted together and poked up in the ceiling void. Often the earth was not used for anything, regardless if metal light fittings were used or not.

Or sometimes the earths were just cut off.

Nothing was particularly black and white about wiring methods then.

Other houses in the 50s had their sockets wired in 2 core twin early pvc cable, with a bare stranded earthed cable run next to it.

In those days you used what you had, it seems.
 
Other houses in the 50s had their sockets wired in 2 core twin early pvc cable, with a bare stranded earthed cable run next to it. .... In those days you used what you had, it seems.
Yes, as I said, the remnants of sockets wiring here seemed to mainly have a bare (stranded) 'earth' wire alongside (often stapled in place) - and I think they may well have been steel - certainly something far tougher (more difficult to cut!) than copper.

Kind Regards, John
 
You know, it makes me wonder if in 1966 the cable companies may have had large supplies of red sheathed and insulated single core that they had no hope of selling, and simply 'welded' a single insulated green earth core to it...
 
You know, it makes me wonder if in 1966 the cable companies may have had large supplies of red sheathed and insulated single core that they had no hope of selling, and simply 'welded' a single insulated green earth core to it...
That would make sense.

Kind Regards, John
 
Seen this today 1960s house been rewired this is the old cable for the switch drops ....View attachment 233316View attachment 233317
Not sure why I haven't seen this thread before.
That's the old 3/0.029 single and earth. Different makes did it either like your picture or more commonly like T&E;
IMGP2666.jpg

By the way don't use this method to wire lights.
 
Last edited:
I have seen that cable before a couple of times, the one with the CPC attached.

Odd stuff.
 
I have seen that cable before a couple of times, the one with the CPC attached. Odd stuff.
Sparkwright's suggestion sounds pretty credible - that, come ~1966 some manufacturers had lots of insulated-and-sleeved singles for which there was little continuing market, so they stuck green-insulated CPCs on the side to turn them into something more 'saleable'?

Kind Regards, John
 
I'm not so sure.

I&S cables, both with and without CPC, were commonly used well into the 1980s.

This coincides with the very last installations done under the 14th.
 

DIYnot Local

Staff member

If you need to find a tradesperson to get your job done, please try our local search below, or if you are doing it yourself you can find suppliers local to you.

Select the supplier or trade you require, enter your location to begin your search.


Are you a trade or supplier? You can create your listing free at DIYnot Local

 
Sponsored Links
Back
Top