If I recall correctly, the CPC can be smaller than live conductors provided it complies with the adiabatic equation.
Could be a bad connection. When does the tube flicker, all the time?, only when the outside light is on etc? Do you have a switch on the...
You can buy windows, soil piping and even gas boilers from the Sheds so why do you think they will stop supplying electrics?
My money is on a blockage ... but if you keep using it it will be u.s. If its stand alone, turn it off, isolate water, remove tail pipes, trip...
Sorry to be picky but unless you have TT all supp. bonding needs to be 4mm. (Table 10a/b of the osg if memory is right)
Yes. Just remeber the permitted route regs.
Strictly to self certify you only need 2381. However you do need to be a full time employee of the firm, have £2M Public liability insurance,...
Are you sure a single 2.5mm cable run without mechanical protection is allowed? I thought it needed to be 4mm? I understood there can be...
I use heavy duty wire cuuters but a sharp stanley knife works just as well. Don't try and cut all the way through, a gentle repeated circular...
Hi, We answered a similar question today, and a couple yesterday. Do a search and if you are still stuck reply again to this topic. BN
Thanks for the info.
Maybe ken has bigger plans? :twisted:
Difference comes from allowing for diversity. 30.5A is the max the hob can draw. However how often do you have all the plates on at once?...
Have you tried balancing the system? Are all the lockshields fully open upstairs?
Joy of batteries and RCBO's.
Echo delmel. I can recall a couple of similar topics recently. Before you start running sub mains I'd consider if its possible to split into...
7kw -- 7000 /230 = 30.5A Allowing for diversity 10 + (30% 20.5) = 16.2A Therefore how they get to 13A is beyond me. 16.2A would require...
Glad to hear its fixed. If you still have a copy of his advert why not send it to CORGI and/or your local trading standards. You were smart...
Both Wylex ... depends on if you want metal or plastic. Insulated would be needed if you have TT with main RCD in the CU.
Errmm instinct tells me:- no, it’s not going to be simple for you. Firstly there are lots of posts covering similar problems. However here goes...