  1. N

    Baxi 80e combi boiler.

    they can't really be cleaned. Apart from the gismo the bg lads have. I'd replace.
  2. N

    One for the baxi lads

    customer says they havn't but it could have been. Very hard water area but the stuff he left in a bowl was black and half a circle shape. Definatley from the heating side. I have had same problem before on older systems but i always do an 8 hour flush on an older systems and cleanser on new systems.
  3. N

    Baxi 80e combi boiler.

    could be a hole in dhw diaghram but i find you can't really clean the plate heat exchanger so may need a new one. Was they lots of black shale in it?
  4. N

    One for the baxi lads

    sorry i forgot to add it has a magnaclean on :lol:
  5. N

    One for the baxi lads

    6 month old installation. Re ferb house. All pipework, rads changed and i mean every single pipe. New Platinum 40HE fitted. Customer had no hw. Called Engineer out today who found a blocked plate heat exchanger. He fitted a new one but told my customer that the system wasn't flushed correctly. I...
  6. N

    Hoval Topgas condensing 45-4 KW... thoughts?

    lets hope that Remeha apply the Honeywell MBA control system to the baxi & potterton now that they have bought them as i am getting a little sick of E168 on there duo tecs :lol:
  7. N

    Pressure problems

    what size expansion vessel did you fit? did you fit it on the return? and what pressure is the external expansion vessel charged too?
  8. N

    just fitted TRV struggling to get rads on afterwards

    sounds like an air lock. is all the system full and rads bled? what boiler do you have? and what is brand of pump?
  9. N

    leak under concrete floor

    how much of your system is under concrete? It's never advisable to run copper under concrete as it rots and pressurising it will find all the little pin holes. Best advice it to repipe any under concrete pipework. 10mm plastic will work but i have always been a 22mm copper circs man and...
  10. N

    suprima

    may be a daft one but have you checked polarity? and voltage difference. Had it before where there was 30v on the neutral which sent the pcb a little hellwire.
  11. N

    Powermax 155x advice please - Vent and Pump Relay faults?

    only met the guy once but he made an impression. I have a mixed bag of tricks with commercial and being bonus direct but i often recomend your fixed price repair as it can work out alot cheaper in the long run sometimes.
  12. N

    Baxi 80e fan/flu fault

    no pal i contract for baxi commercial. I play with the big boilers whislt you play around with up to 40kw?
  13. N

    Potterton Suprima HE 50

    just make sure the compression joints that conect to the flow and return don't weep as they are still prone to rotting through the casing.
  14. N

    Potterton Suprima HE 50

    no complete re design on the electrics
  15. N

    Powermax 155x advice please - Vent and Pump Relay faults?

    i bet Mr Robinson wouldn't be happy that your giving advice on here when he could be selling repair pluss ones instead????
  16. N

    Megaflo cold water combination valve & TPRV

    on the front of the cylinder there is a sticker that tells you how to do it
  17. N

    Powermax 155x advice please - Vent and Pump Relay faults?

    best advice with a powermax is call Heateam. Their boiler and they are the experts
  18. N

    Baxi 80e fan/flu fault

    my diary is full until March. I don't have to advertise either.
  19. N

    Baxi Duotec 28 He Combi Boiler

    only things that can cause E133 are 1) electrode spark gap 2) ignitor unit 3) fan venturi tube kinked 4) gas valve I find every 12 months the electrode needs the spark gap adjusting
  20. N

    Baxi Duotec 28 He Combi Boiler

    electrodes needs bending back. Spark gap is prone to reduce with heat. No parts needed but a gsr to do it