And what happens if an extra 35A is drawn - where will that safely go?because the cable is sized correctly for a 40A CPD and the load is fused down at the connection point with an FCU.2. Why do you believe that a 40A CPD is ok for my proposed radial with a 5A loading?
I apologise if you've had to repeat your answer, but that's the first time I've noticed you saying that you can't think of any risk.no I can't ( as I've already said at least twice in answer to this question you KEEP asking ), but likewise I see no risk arrising from leaving the 30A in place and connecting the equipment with FCU's as is the OP's intention..3. Can you think of any risk that arises when using a 30A breaker/cartridge on jpbunce's radial final, that either doesn't arise, or is to any extent mitigated, when using a 10A CPD?
I really thought you would, but there's still a chance that someone else will.