I am about to install a new kitchen. Within the space of about 300mm, it has a single socket on the 30A whole house ring, a 30A cooker point and a redundant 15A immersion heater supply. The ring also has another socket in the bedroom immediately above.
I need sockets under the counter for a washing machine and a slot-in gas cooker. I also need a fused spur for a nearby combi-boiler on the next wall.
If I put a terminal block in the existing ring socket, I could extend the ring for the two under-counter sockets. I'd only need to chase a pair of cables 200mm below the counter and run the new section of ring on the surface behind the units.
This still leaves the new fused spur for the boiler on the next wall. I could put another terminal block in the bedroom socket and extend the ring down to the fused spur for the boiler on the next wall. Can I put this in the wall above the boiler?
I need sockets under the counter for a washing machine and a slot-in gas cooker. I also need a fused spur for a nearby combi-boiler on the next wall.
If I put a terminal block in the existing ring socket, I could extend the ring for the two under-counter sockets. I'd only need to chase a pair of cables 200mm below the counter and run the new section of ring on the surface behind the units.
This still leaves the new fused spur for the boiler on the next wall. I could put another terminal block in the bedroom socket and extend the ring down to the fused spur for the boiler on the next wall. Can I put this in the wall above the boiler?