Recent content by bensp

  1. B

    Viesmann 100-W boiler - pump keeps kicking in

    Hi, I popped the capacitor on and the problem is now resolved. Many thanks to everyone who offered up information. I have quite enjoyed looking at this and all though I would call the installer back for anything more serious I am happy to tinker around the edges as I find this stuff...
  2. B

    Viesmann 100-W boiler - pump keeps kicking in

    Hi The capacitor has arrived form Viessmann and I just wanted to check before fitting, if I could. The wires form the capacitor block just need bending to allow me to fit it into the case - no problems there. On the PCB I to the left of 96 I have wires for earth live neutral all...
  3. B

    Viesmann 100-W boiler - pump keeps kicking in

    Thanks for all the info. As I don't have a capacitor I will ring Viessmann in the morning and order the capacitor. I would think to fit it I just turn the power off and place it in-line between the PCB block (N/1) and the two wires. Thanks
  4. B

    Viesmann 100-W boiler - pump keeps kicking in

    Thanks agile. Does anyone else know for sure if these are the right capacitors? If not then I guess I will have to pay the price and have viessmann take a look...
  5. B

    Viesmann 100-W boiler - pump keeps kicking in

    I see 1 and N on the PCB where 96 is marked and just behind there are two small blue capacitors, does that sound right? Thanks
  6. B

    Viesmann 100-W boiler - pump keeps kicking in

    Sorry it has taken so long to post back I have been a bit caught up. Anyway I did the trouble shooting as described and found think all components are working correctly. However I replaced the Honeywell ST699 controls, like for like, as I noticed some scorch marks on the PCB. Perhaps some...
  7. B

    Viesmann 100-W boiler - pump keeps kicking in

    I will run through the guide but I don't have any issues with water/heating cutting over just the boiler triggering the pump. How would the valve cause that or is this just a good place to start checking? Thanks
  8. B

    Viesmann 100-W boiler - pump keeps kicking in

    Hi, I have a hot water cylinder with 3 way valve also honeywell. I had it replaced about 8 months ago and i can hear it switching between hot water and heating. I have never seen the hot water symbol on the boiler but the water does get heated up fine. Thanks
  9. B

    Viesmann 100-W boiler - pump keeps kicking in

    Ok I take your point on isolating the controls. I would think I have to remove the wire within the boiler or the control casing in effect. I will have a look. On a side note do you know if there are any controls which work well with Viesmann? There site lists a couple but they only...
  10. B

    Viesmann 100-W boiler - pump keeps kicking in

    To be honest I am not sure. I thought the boiler would not fire up if there was no signal as such from a controller. I think because the weather has become a bit warmer I noticed it more so than when it was cold and the installer thought it might just be pump over run. If there an easy...
  11. B

    Viesmann 100-W boiler - pump keeps kicking in

    Hi, First post on this forum so go easy. I have searched the forums for my problem and as I have found nothing I think it must be one of those silly niggles that is unique to me! My boiler is a Vitodens 100-W WB1B regular open vent. My controller is Honeywell, timer box on the wall and...