  1. D

    BIASI 28S Excessive Water Pressure

    Hi All It sounds like I need a new heat exchanger then. Removing the filling loops only, made no difference. When drained and off, the pressure stayed down. As soon as I turned it back on, it rose straight back to 2.5 bar. And the overflow still leaks all the time. that is probably another...
  2. D

    BIASI 28S Excessive Water Pressure

    Thanks guys, will try the draining and removal of the filling loop when I get home tobight. I did wonder why the loop was still in place as it says in the installation guide to remove it. Maybe left to ensure it does not get lost if needed again. Cheers :?
  3. D

    BIASI 28S Excessive Water Pressure

    Thanks for that, filling loop definitely switched off.
  4. D

    BIASI 28S Excessive Water Pressure

    Hello I have just completed on my new house and moved in. I have a BIASI 28s boiler. Water is escaping from the overflow, not excessively, but enough for a non DIY fundi to notice. I checked the water pressure gauge to find it registering 2.5 bar and know that is too high, yet I am unable...