    Hi, I have come to the conclusion that I do not have sufficient flow /pressure for a high flow std combi. Can any one recommend a storage combi. i.e. one that has a ready store of hot water, 60-100 litre, that starts to be replenished as it is used. I have approx 12 l/m at 1 bar to feed...
  2. E

    pressure for a combi

    Hi have taken some further readings. Static 2.2bar. flow 4 l/m @ 2 bar flow 8 l/m @ 1.5 bar flow 12 l/m @ 1 bar flow 15 l/m @ 0.5 bar flow flow 18 l/m @ valve fully open. When the Combi data gives the required inlet pressure for max DHW flow I assume it is flow pressure so I recon I...
  3. E

    pressure for a combi

    sorry I meant 20m head and 6m head. The gauge had a full scall deflection of 2 bar (20m head). The greenstar high flow 440 (DWH 20 l/m) tech data says 1.5 bar inlet pressure for max DHW rate. so why am I getting only 12 l/m at the tap with 2 bar?
  4. E

    pressure for a combi

    I wish remove the airing cupboard and have a better shower so a high flow combi ( 2 bathrooms and 5 adults). Taking advice from the forum I had 3 plumbers including the gas board for a quote. No used a pressure gauge and visually checked the flow from the kitchen tap and said not enough...
  5. E

    ATMOS Multi Boiler

    Hi has anyone any comments / experience of the Atmos Multi boiler. I wish to move the hot water cylinder out of the bedroom and also have a power shower. I have a 25mm mdpe supply in to the house but can still only get 12 l/min. so for a 4 bed 2 bath a standard combi set up will be no good...