    Ecoflam minor 1 models and "Burbling" B52 burner

    Stuartt, you're right but I sorted it yesterday. Thanks for replying. As a pointer for others it turned out his flue was probably partially blocked after a few days of driving wind and rain here. I found the cause by removing all baffles and then firing the boiler. It ran almost perfect as it...
  2. J

    Ecoflam minor 1 models and "Burbling" B52 burner

    It does. The flap is free to move. The air intake is on the RHS as you look at the burner situated in the boiler. I've seen ecoflams with the air adjustment on the intake round inlet, but this ecoflam has a horizontal slot numbered 0 to 9 on the back of the burner. There's a bolt head. Loosen it...
  3. J

    Ecoflam minor 1 models and "Burbling" B52 burner

    Hi Stuartt did you ever get to the bottom of this problem? I have a customers burner doing exactly the same. I changed the fuel pump because it was leaking past the seals and it came with a new solenoid. Set pump at 100psi and no change to sooting smoke from burner. Definitely running rich...