pressure is 1.5 bar cold 2.2 hot found valve no probs. i realise the releif valve is releasing the pressure prematurly so will get new one ... thanks guys for your help
are these relief valves easy to fit ?
i know the pipe side of the valve is just simply undo the nut but does the other end the one with the O ring on it is that a push fit or what ... cant make it out from picture i have here..
thanks again
ok what ive just done is opened and closed the releif valve a few times to try and expell and dirt that might me trapped within the valve seal.
repressurised to 1.5 bar and bressure has gone to about 2.2 bar but water has started leaking from pipe outside ( the one connected to the valve...
need help i have baxi combi 100 he plus boiler keeps loosing pressure - i have checked for leaks and found none.
the boiler is losing pressure from 2.5 bar and then tripping the ignition lockout at 0.5bar.
i have repressurized the vessel to 2.5 bar but still loosing pressure.
repressurized at...