  1. L

    Overheating boiler

    Yes that was the problem. A new sunvic 2 way valve fitted,the old one was stuck half way. Thanks for the advice. :D
  2. L

    Overheating boiler

    No turned off.
  3. L

    Overheating boiler

    I'm not sure of what type of plan it is but I think it is a pumped system not gravity.As I said there is no current at the tank stat.There are 5 wires running from the 2 way valve,3 from the stat and 2 from the mains.From the mains the red wire goes to the brown from the stat and the black goes...
  4. L

    Overheating boiler

    Hi first time post so I hope I'm not repeating something.My hot water is coming out of the taps at 90 degrees with the tank stat set at 50! I changed the stat for a new one but does not seam to have solved the problem.There is no electrical current going to the stat although there is current at...