Recent content by mikil

  1. M

    Obsolete boiler parts

    Quick update Boiler now up and running. Obsolete part number contains the manifold and new seals. Manifold no longer produced but the seals are still readily available. As someone said earlier. The only thing out of the obsolete pack required was the 1 seal for in between the gas v/v and...
  2. M

    Obsolete boiler parts

    Just spoke to SSE questioned why he says gas valve and they say manifold assy kit. Apparantley to replace the valve you have to remove the manifold meaning you need new seals from the obsolete kit to rebuild safely. They spoke to the eng and he says he can do it with seals from another seal kit...
  3. M

    Obsolete boiler parts

    This is first time an eng has been at the boiler except for service so dont think its been damaged by anyone.
  4. M

    Obsolete boiler parts

    No idea whats wrong with it. Boiler intermittently not igniting last week then last Friday gave up for good. When i put the boiler on it powers and it sounds like the fan is running but it wont ignite and there is a faint clicking in the background. Engineer came out on Saturday. Said it needs a...
  5. M

    Obsolete boiler parts

    Hi thanks for reply. Just called them they dont have it. Had an argument with SSE yesterday regarding me finding one and them fitting it. They only use a certain list of suppliers and wont fit from anywhere else. Apparently boiler manufacturers only have to make spares for 10 years afrer they...
  6. M

    Obsolete boiler parts

    Hi can anyone help out here. I have Ideal classic se21 ff boiler. It stopped igniting a few days ago. Covered by SSE hydro for repair but the part the eng says it needs is now obsolete. As they cant source the part they say i need a new boiler. They cancel my contract and walk away with all the...
  7. M

    Boiler Breakdown Xmas Day

    After all day yesterday and most of today with the fan going but no ignition the boiler suddenly burst into life. The only thing i did do today was spray the fan bearings with some lubricating spray, could this have helped? I will still arrange for an engineer to check after the bank holiday.
  8. M

    Boiler Breakdown Xmas Day

    Thanks, i can cope till tomorrow. Couldn't have happened at a worse time.
  9. M

    Boiler Breakdown Xmas Day

    Thanks, That is probably what i will do, as i did say in my post. The question im asking is are there any user resets or things i myself can check. I will call someone tomorrow as the temperature today is liveable and i do have an immersion for water.
  10. M

    Boiler Breakdown Xmas Day

    Hi all, i have a Megaflo unvented system with an Ideal classic se21FF boiler downstairs. Woke up yesterday heating and hot water had both been on in the morning. But when i tried to put it back on for more water the boiler would not fire up as normal. The boiler will not ignite for heating or...