    Potterton Profile 80e keeps shutting down

    That's the problem. I can't bleed any air from the rads and I've done the glass of water under the vent pipe and the level didn't change.
  2. M

    Potterton Profile 80e keeps shutting down

    The instructions on the bottle are pretty vague. It says to leave in for at least 2 hours or for best results overnight and then says it can be dosed up to 3 weeks prior to draining. So 2 hours, 24 hours, 3 weeks or 5 weeks? It's confusing and I felt a week should do, too late now though...
  3. M

    Potterton Profile 80e keeps shutting down

    A quick update on my problem. I ended up getting a plumber round and he agreed that there was air in the system and suggested draining down and refilling 'bottom up' from the draincock. I did this with a bottle of Sentinal X400 cleaner and left it for a week. Then I drained down, flushed a...
  4. M

    Potterton Profile 80e keeps shutting down

    I don't think it's boiling as the noise isn't that loud. It's more like a large amount of air releasing and it glugs up into the flow pipe. Difficult to explain via a keyboard.... I'm wondering if the automatic vent (which is situated on the return just before the boiler) is sucking air in...
  5. M

    Potterton Profile 80e keeps shutting down

    That's a good question Bernard, and I don't know for sure to be honest.... Although I think it's probably air, as the boiler gives a glug like its releasing a large bubble of air, which then gets broken up as it passes through the pump sounding like a stream of small bubbles...... If that...
  6. M

    Potterton Profile 80e keeps shutting down

    Surely it's the overheat stat that's shutting the boiler down? :unsure:
  7. M

    Potterton Profile 80e keeps shutting down

    I've had another go at this today. Firstly I went along the feed/vent pipe with a magnet and found nothing. Then I drained the system and it drained down quickly and there was good pressure coming out of the hose. After that I untied the ballcock and let it flow through the system for a...
  8. M

    Potterton Profile 80e keeps shutting down

    Will a fridge magnet do? I put a bottle of Primaflow cleaner in when I refilled it on Friday, but I'll get a bottle of Sentinel tomorrow for when I refill again.
  9. M

    Potterton Profile 80e keeps shutting down

    Yes. I ran it for a while last night with the bleed screw off and some air came out, but mostly water dribbling out.
  10. M

    Potterton Profile 80e keeps shutting down

    So I've run the system this evening with the vent pipe over the F/E tank in a glass of water and all that happens is that the water level goes up and down a few millimeters. I'd discounted a blockage in the cold feed pipe as it drained down and filled up again, but I may have another look at...
  11. M

    Potterton Profile 80e keeps shutting down

    It has a combined feed vent (Y plan?) and I did wonder about a blockage but it drained down and refilled without any issues.... The feed/vent pipe is tee'd just after the outlet from the boiler and before the pump and I can't see what speed the pump is on as it's tucked behind the cylinder...
  12. M

    DHW has no pressure

    Another good suggestion thanks! This ones in a rental, so I won't be able to get there until next week. So now I've got a couple more things to check before I call the plumber. Thanks again!
  13. M

    Potterton Profile 80e keeps shutting down

    No, but had new 3 way valve about 3 years ago.
  14. M

    Potterton Profile 80e keeps shutting down

    I'm really puzzled by this. How in an open vented system can air get in? and why is it not venting out via the F/E tank? Although I'm not an expert and I might be wrong, my feeling is that the boiler is OK as it runs fine for about 20 minutes and then air starts glugging and the boiler shuts...
  15. M

    DHW has no pressure

    Not especially. The boiler that this one replaced was a 20 year old Worcester combi which went on and on with no problems, until it eventually died from a leaking heat exchanger. I think modern boilers are crap! I'll try taking the strainers off the taps to see if that makes a difference...