    Central Heating won't come on, but boiler works OK

    Problem solved! Perfect, thank you very much.
  2. P

    Central Heating won't come on, but boiler works OK

    Right - problem isolated. Great tips/advice seco services! The motor isn't moving far enough to push the micro switch - and it sounds weaker than maybe it used to (I can't really remember). If I manually close the micro switch the boiler fires up. Do I make the assumption that the...
  3. P

    Central Heating won't come on, but boiler works OK

    The valve is an old Honeywell "Sundial Y plan 3 position Diverter Valve" - there's no apparent model number on it though. I have a spare one that came with a second hand pump a while ago which is an iflow "Mid Position Actuator" model MA 1. Is this interchangeable with the above should I need...
  4. P

    Central Heating won't come on, but boiler works OK

    Thanks Seco - at least that part seems to be correct :)
  5. P

    Central Heating won't come on, but boiler works OK

    OK, I'm using the blue as neutral i.e. where the blue wire goes into the connection strip. This also reads as live on the grey wire even when neither HW or CH is on. BTW, this did all work as it should last spring, and the HW has been working as it should all summer. Just a guess here...
  6. P

    Central Heating won't come on, but boiler works OK

    Hi both I'm not really sure what I'm doing :) But... Grey | White HW X 0 CH X X CH+HW X X X denotes power. Is the above correct?
  7. P

    Central Heating won't come on, but boiler works OK

    Hi all I hope that this is a simple problem. I just tried to turn my central heating on this morning, but the boiler doesn't fire up when the timer is advanced. The boiler fires up for hot water heating OK, and the 3-way valve seems to work when the CH timer is advanced to 'on' - I can...