    Fixing Metal Trunking/Channel to brick wall

    Ah ok, I understand. So the small load absorbs the energy rather than it leaking to earth? Had I used plastic channel as opposed to steel, might I have not got the problem? I have also noticed that the voltage measured varies. First thing yesterday it was <1v AC and after a mornings work in the...
  2. R

    Fixing Metal Trunking/Channel to brick wall

    Brilliant - thank you very much.
  3. R

    Fixing Metal Trunking/Channel to brick wall

    Thank you for this. What meter would you recommend to avoid this? Cheers.
  4. R

    Fixing Metal Trunking/Channel to brick wall

    A bot of a strange one. I have chased out a wall, moved previously surface mounted cables below the plaster, screwed (carefully) 25mm steel channel and noticed that there is a measurable voltage of around 20 to 30 volts between the steel channel and earth. I have taken the channel off, carefully...