  1. S

    Worcester Heatslave. No lockout, no spark.

    I'll reply to my own question. Yes it is the control box. The lockout button has been slightly melted by whatever has burned out inside it.
  2. S

    Worcester Heatslave. No lockout, no spark.

    It's a 15/19. Stopped heating. The fan kicks in on the boiler, but there is no spark, at least nothing I can see through the hole if I pull the photocell. I would expect it to be locking out, but it doesn't. I'll have a look at the wiring diagram, but does the lack of lockout suggest the...
  3. S

    Worcester Heatslave 15/19 runs then locks out

    Well just to update. Yesterday I reset the lockout about 5 times. Was doing it because I was getting some warmth out of the radiators and meant we had hot water. The lockout was becoming increasingly less frequent, such that I last reset it at around 16:00 yesterday and it's run for about 21...
  4. S

    Worcester Heatslave 15/19 runs then locks out

    Ta. I'll look at that later, and I'll confirm the solenoid coil hot / cold resistance too. I did clean the baffles at the start of winter, so hopefully nothing untoward in there.
  5. S

    Worcester Heatslave 15/19 runs then locks out

    Thanks. Will take me a couple of days to get a new nozzle. No one vaguely local has one of the same spec in stock. Will update. This morning, from overnight cold, it ran for about 20 minutes, and then stopped on the hot water thermostat. When the diverter valve changed to CH the burner fired...
  6. S

    Worcester Heatslave 15/19 runs then locks out

    Thanks guys. Plenty of oil coming through, I have had the flexi hose off. And I beld the pump using the commisioning instructions; port open with the boiler running, spraying kerosene into a bowl. Repeat 3 times. It is an RS model. Have been running it with the cover off just because I have...
  7. S

    Worcester Heatslave 15/19 runs then locks out

    Thanks John. I will get a new nozzle. New coil was fresh from the sealed packet, but the old and the new can be felt exerting magnetic forces on a screwdriver when detached from the solenoid. It all sounds normal. Fan starts, can hear the ignition and the burner kick in. Runs for a bit and then...
  8. S

    Worcester Heatslave 15/19 runs then locks out

    Boiler locked out over the weekend. Oil was very low, in fact I assumed we'd run out; although in hindsight I don't think it was that low. Got a full tank today but the boiler runs for about 5-10 minutes, enough to give us a storage tank of reasonably warm water, and then locks out the burner...