cheers plugwash,
Yes it is a dedicated circuit. Planned to use a 45A DP switch with min 3mm sep, will use a 20A breaker.
Good news for me as i didnt fancy the aggro and destruction of running a 4mm cable.
Thanks for the advice :D
Hello
I've recently purchased a Baumatic double oven rated at 3.95kW,the manufacturers instructions say it should be connected to a 20A supply(?).I currently have a single oven connected to a 13A fuse spur (i didnt put this in) on a 2.5mm cable about 5m run length back to consumer unit.
If I...