    HW but no CH but it's not the 3way valve?

    THANKYOU all whom helped me here. I have tested the voltage and changed the junction box as a result and now have it all up and running!!! CHEERS!!!!!!!!
  2. S

    HW but no CH but it's not the 3way valve?

    When i turn on the CH the light comes on at the programmer but nowt happens. I'll have a tinker with the voltage testing but not sure what i'm looking for.
  3. S

    HW but no CH but it's not the 3way valve?

    Hmm. i thought that as i had swoped the 'on wires' around that this proved it wasn't the programmer as the HW wouldn't of worked.
  4. S

    HW but no CH but it's not the 3way valve?

    I've replaced the whole head of the valve with no luck. If i manually move the lever and turn the HW on it will heat up the rads so guess the valve is not stuck. I'll give the electric test a go, anyone know a good guide of what i'm looking for though. Cheers
  5. S

    HW but no CH but it's not the 3way valve?

    Hi, My pump got dripped on and blew. i changed it but now the HW comes on fine but nothing happens when i turn on the CH. i changed the 3way valve motor but no luck. I swoped the CH 'on' and HW 'on' wires in the wiring center and it fired up so i guess it's not the programer. Room and Tank...