Search results

  1. J

    sunvic upgrade ch comes on with hw

    Thanks for all your input, it looks as if Boilerman2 was right “2) A totaly new fault has occurred possibly the motorized valve.”. Taking the powerhead off and manually moving the spindle cures the problem ie. HW only is delivered. New powerhead in place and all is well. Many thanks.
  2. J

    sunvic upgrade ch comes on with hw

    Gravity or Pumped can be selected but no option regarding port. , dip switches identical to 207xl, instructions for which can be found at http://www.sunvic.co.uk/documentation/Programmer_Select_207.pdf
  3. J

    sunvic upgrade ch comes on with hw

    :D re: "played" Yes it did, replaced as early signs of contact failure were observed, contact bounce (chatter), that’s why im bamboozled. Planning to try a replacement 207xls prior to condemning the 3 way valve.
  4. J

    sunvic upgrade ch comes on with hw

    I used the original one and kept the new one as a spare. Regards
  5. J

    sunvic upgrade ch comes on with hw

    Just thought its worth mentioning that I found it unusual that there is no connection to the back plate terminal for CH off (terminal 2). i.e. Only 5 cables present/connected, not 6 as per wiring diagram . It’s not a particularly old system as the house is only 10 years old. Regards. :? :?
  6. J

    sunvic upgrade ch comes on with hw

    Unfortunately, even with room stat turned right down, selecting HW only results in the radiators heating.
  7. J

    sunvic upgrade ch comes on with hw

    Following upgrading the programmer from a Sunvic 207xl to a Sunvic 207xls the HW no longer runs independently to CH. Following the upgrade; selecting HW only results in the radiators becoming heated. It was noted that backplate configuration was N/ L/ HWoff/ CHoff/ HWon/ CHon, (the backplates...