    sterling10lcd

    You are a rock-star....thanks.......it was reversed pos and neg at the pir's......couldn't see it for looking at it.......magic thanks.........got another question now....lol.......see the attached documents............for the internal sounder it says connect to BA / SPK but I do not have these...
  2. Untitled

    Untitled

  3. Untitled

    Untitled

  4. Untitled

    Untitled

  5. boybilly

    boybilly

    photos
  6. B

    sterling10lcd

    The panel is Sterling 10-8 Zone - Sterling 10 PS10LCD and the PIR'S are Pyronix MEQ blue quad PIR detector.
  7. B

    sterling10lcd

    The terminations in the PIR are 2 for tamper, 2 for aux and 2 for N/C, 1 being N and the other being C. You do not have an option for N/O. Then at the panel you have 2 terminals marked zone which I terminated the 2 cores into which I had N/C at the PIR. It's a strange one. Thanks for efforts...
  8. B

    sterling10lcd

    No joy, I took the 4 fuses out and re-checked, all ok. 2A Battery Fuse 2A AC Fuse 1A Aux Fuse 1A Bell Fuse I am getting approx 14v at each PIR and the tamper operates, I am just getting an open loop at pir on the N/C terminals, I linked these out to prove the cores ok and they were. Strange...
  9. B

    sterling10lcd

    OK, thanks,I will try that and get back to you.
  10. B

    sterling10lcd

    Hi, With my Fluke (muti meter), checked for continuity. Thanks.
  11. B

    sterling10lcd

    sorry, yes checked 4 off glass fuses........all ok........
  12. B

    sterling10lcd

    Thanks for your reply, I have checked the glass fuses x 3 but I will double check to ensure I have not missed one. Thanks.
  13. B

    sterling10lcd

    trying to commission panel but it is not picking up the pir's. the pir's are showing normally open but should be closed. disconnected the pir's from the panel and linked out the zones at the panel, the panel then would arm. but when reconnected the pir's back in the the panel would not arm. the...
  14. B

    pyronix security

    Hi all, Have recently installed a sterling pyronix security system. Have wired the 7 zones back separately but when I go to arm the system it flashes up zone 7. I omit this and try again, but then it flashes up zone 6. And so on. So I omitted all the zones and it would let me arm the...