  1. D

    strange shower electrics problem

    i'm guessing the landlord put the original shower in himself. and i'm an idiot for not checking everything before replacing it. so let me get this straight - on a 32a circuit, the shower should be no more than 7kW. i need to get an electrician in to assess the wiring, to see whether its the...
  2. D

    strange shower electrics problem

    no - apparently it had been in for 6 years with no problem until the switch broke
  3. D

    strange shower electrics problem

    the shower i took out was a 10.5kw - i thought it best to go with something the same
  4. D

    strange shower electrics problem

    cheers man, but i'm still confused as to why it happens when its isolated...
  5. D

    strange shower electrics problem

    its an MCB
  6. D

    strange shower electrics problem

    hello - i've got a weird problem with the shower - the RCD trips when the shower is off, and the isolator pullswitch is off. sometimes at the same time as the pullswitch is turned off usually a few minutes later. its a protek b32 RCD, and looks newer than the rest of the RCDs in the panel...