  1. 'aveagoJo

    boiler cuts out shortly after firing up

    Mate, you never believe it!;I did it! I pushed and prodded wrestled with it all afternoon and then finally it dislodged and the water flowed out . What a joy. The heating is back on! Fantastic Thank you so much for all your help. It's been Brilliant having you and Terry there to guide me ...
  2. 'aveagoJo

    boiler cuts out shortly after firing up

    Yes go to idea I have been trying but there's a corner (ref previous photo) can't push past there
  3. 'aveagoJo

    boiler cuts out shortly after firing up

    afternoon! ok, so I had a go and have disconnected the pipe configuration from the pump as you suggested. the F&E tank is clean as a whistle and I popped some water into it when i let it run nothing came out!! Have also discovered a gate valve half-way up the cold feed. So i disconnected it...
  4. 'aveagoJo

    boiler cuts out shortly after firing up

    Well thanks to you both. This has been really helpful. I'm done for the evening but will try again tomorrow. Thanks for taking an interest, I'm really grateful.
  5. 'aveagoJo

    boiler cuts out shortly after firing up

    Horizontal pipe, sticks from join on and around corner
  6. 'aveagoJo

    boiler cuts out shortly after firing up

    Checked the 2vertical pipes. Magnet does not sticking all the way up
  7. 'aveagoJo

    boiler cuts out shortly after firing up

    No the magnet is not sticking there
  8. 'aveagoJo

    boiler cuts out shortly after firing up

    Yes I do have an upstairs. No water coming for the rads up here. I think a lot of water had left the system today. Are you suggesting just bleed an individual rad?
  9. 'aveagoJo

    boiler cuts out shortly after firing up

    Ok so I have used my magnet. Not sticking to the feed pipe as far as I can tell. But. It is sticking to the pipe directly above, and leaving, the pump. Also sticks to the horizontal pipe leading to the air release valve
  10. 'aveagoJo

    boiler cuts out shortly after firing up

    This is an old photo, For your reference the pump is not currently on and I plan to turn down the speed. Right, I'm off to find a magnet
  11. 'aveagoJo

    boiler cuts out shortly after firing up

    excellent! suggestions? fixable? what might cause this?
  12. 'aveagoJo

    boiler cuts out shortly after firing up

    Hi terryplumb, i have drained a few litres from the system. The water level in the F&E tank has not moved. :( I dread to think what this means.
  13. 'aveagoJo

    boiler cuts out shortly after firing up

    thanks John. Yep the pump arrow is pointing upwards. Been in place for about two years and not been a problem. I have never been sure what the correct speed should be, so thanks for your advice. I will ensure it is as you suggest.
  14. 'aveagoJo

    boiler cuts out shortly after firing up

    Yes. Boiler reacts same way HW or CH. So, by drain the system you mean the entire CH system? May have to do that in the morning.
  15. 'aveagoJo

    boiler cuts out shortly after firing up

    Hope these pictures work