  1. K

    Vokera DHW

    Thanks Chris R - apologies for delay in reply as I do not have a computer at home. Will look into the thermostatic mixer this weekend and also drain boiler down to clean out although living in a soft water area and with the boiler being only 3 years old I would be a bit surprised
  2. K

    Vokera DHW

    Thanks Tony we can fill a bath no problem through the taps. Although will try your suggestion tonight. Might it be a strainer issue on the inlet to boiler or on the thermostatic valve as they may be restricting the flow which in turn may cause boiler to cut out
  3. K

    Vokera DHW

    Thanks Agile will do. Yes the DHW from basin taps seems ok. Forgot to say the problem appears a lot worse when the central heating is on. Might this be a potentially larger issue or is there too much demand on the system?
  4. K

    Vokera DHW

    Have a vokera compact 28 combi-boiler approx 3 years old working fine until recently. However now when using the thermostatic shower the temperature of the water alternates between hot and luke warm/cold. Have replaced thermistors but alas to no avail. The boiler appears to cut out rather than...