Hi,
I am looking for some guidance on installing a fused spur for underfloor heating. The heating mat is 10msq x 200watts so 2000watts total. I have been advised this can be installed off a 13amp fused spur which is fine as I have a double socket and single socket located directly through the wall from the installation (house has concrete floor so it difficult for running cable). My question is can I also spur off the double/single cocket to install sockets in the room of with underfloor heating.
Sockets are to 32amp breakers on the consumer unit.
thanks .
I am looking for some guidance on installing a fused spur for underfloor heating. The heating mat is 10msq x 200watts so 2000watts total. I have been advised this can be installed off a 13amp fused spur which is fine as I have a double socket and single socket located directly through the wall from the installation (house has concrete floor so it difficult for running cable). My question is can I also spur off the double/single cocket to install sockets in the room of with underfloor heating.