Hi guys, I need some advice, we currently have a gas hob and electric oven (oven rated to 2.8kw hard wired and the hob connected to a 5amp fused spur for the spark)
The oven has died and needs replacings, the kitchen is about 14 years old looks dated but the wiring is upto standard AFAIK.
The mrs wants a new silver oven instead of white, which means we need to change the hob too... she also wants a induction hob...
We have the current oven hard wired to the cooker switch which is protected by a 32amp MCB in the CU,
If we fit a 2.85kw oven and a 6/7 kw induction hob can these be both connected to the same cooker connection (not by myself by someone who knows what they are doing), or would we need new cables running to the CU etc,
The cooker switch does not seem to have any fuses on it...would we need to replace this aswell>
If we need to rewire I will either buy a replacement white oven or just get a silver gas hob and wait until we get the new kitchen to run wires..
Cheers
Chris
The oven has died and needs replacings, the kitchen is about 14 years old looks dated but the wiring is upto standard AFAIK.
The mrs wants a new silver oven instead of white, which means we need to change the hob too... she also wants a induction hob...
We have the current oven hard wired to the cooker switch which is protected by a 32amp MCB in the CU,
If we fit a 2.85kw oven and a 6/7 kw induction hob can these be both connected to the same cooker connection (not by myself by someone who knows what they are doing), or would we need new cables running to the CU etc,
The cooker switch does not seem to have any fuses on it...would we need to replace this aswell>
If we need to rewire I will either buy a replacement white oven or just get a silver gas hob and wait until we get the new kitchen to run wires..
Cheers
Chris