Hi,
The prd went on my 7kw Triton T50i shower.
I'm hoping to replace the shower as it is a bit rubbish anyway!
Screwfix have a 8.5kw shower for £40 which would be ideal, but want to ensure the cable etc is up to the job.
I don't know the cable size but think it may be 6mm, will be going in the loft to see if it is marked on the cable tomorrow.
Its a short run from the consumer unit, less than 10m probably.
The circuit breaker is a LN 5945 so 45A? Which is too large really?
Would 6mm cable be acceptable/safe if that's what it is?
Thanks all