Thanks guys, as I really don't know much about electrics.
This is the switch as I'm not familiar with teh terminology, is this dangerous then?[/img]
The hob seems to be this one.
http://www.baumatic.co.uk/b65ss_21_104_15417.html
Says
Electrical details
Rated Voltage: 230 Vac 50 Hz
Supply Connection: 30 A (double pole switched fused outlet with 3mm contact gap)
Max Rated Inputs: 7.00 kW
Mains Supply Lead: 3 core x 6 mm² (not...
I put the electric hob on to try and just heat my new flat up a bit and the fuse blew after 5-7 minutes.
The fuse is in a fused spur, but it is only 13amp, is this too low for an solid plate electric hob? Seems strange, any help most appreciated.
Thanks
Adam