    Glowworm boiler starts and stops

    Thanks folks – I’m most grateful for you taking time to respond. I found that the air pressure switch turning off – as the boiler cuts off, and then found that the fan had stopped working. Although the fan starts working initially – it appears that after few minutes it comes to a stop. Then...
  2. C

    Glowworm boiler starts and stops

    By the way I checked the pump it is working fine.
  3. C

    Glowworm boiler starts and stops

    Glow-worm Fuelsaver 55F boiler cuts off after 2 mins or so of operating. Then everything stops, including the (extractor) fan and I could hear the gas valve shutting. When I checked I found that there is no power (230V) to the fan. It takes a long while to restart – I have to switch off mains...