  1. F

    y-plan not calling Broag system boiler

    Guys , I reset the boiler as advised , put the wiring back to the default and fired her up again . Still no joy . I got my meter out and tested pin's on X2 , which confused me even more , pin5 was Live , { this should be the neutral ? } then it dawned on me , I have been looking for a...
  2. F

    y-plan not calling Broag system boiler

    Sorry guys , I'm currently not able to carry out any tests until Wednesday , I've not put 240V on X9 at any time . But will provide all tests done up to pres. hopefully tonight
  3. F

    y-plan not calling Broag system boiler

    I tried the links ( 3 to 4 ) on X9 , but this just fired on the boiler constantly . The strange thing I picked up from reading Paul's post and also the user manual was I should be able to feed a clock off pins 4[L] and 5[N] on X2 , but I have never had 230V on pin 4 . My setup at pres...
  4. F

    y-plan not calling Broag system boiler

    it's firing up the boiler from the 230V demand feed { from Wiring centre term 8 orange from 3-way valve } , but when I feed a permenant Live , place the 230V demand in term 1 on X2 and remove the links . It starts up but won't call CH or DHW
  5. F

    y-plan not calling Broag system boiler

    Sorry forgot to mention I have already tried just removing 1-4 on X2 , still no joy ....
  6. F

    y-plan not calling Broag system boiler

    Tried it this morning , but it wouldn't fire up again , any other ideas ?
  7. F

    y-plan not calling Broag system boiler

    The boiler is a Broag Avanta 24S and X6 block is fed from Wiring Centre { port 8 }. I knew it was wrong but when I set it up as per the handbook { removed links X2:1 to 4 and X2:3 to 4 then set permenant L/N/Earth to X6:1,2and3 then plugged port 8 from wiring centre to X2:1 as per standard...
  8. F

    Pump/boiler running continuously...

    I now have a similar issue , the boiler is a Broag Avanta 24S and X6 block is fed from Wiring Centre { port 8 }. I knew it was wrong but when I set it up as per the handbook { removed links X2:1 to 4 and X2:3 to 4 then set permenant L/N/Earth to X6:1,2and3 then plugged port 8 from wiring...