Thing is if i click the little things so its not set to come on then then it doesnt. its when the clicky things are set it comes on even if the boiler is set to off..
Hi all i have a glow worm 24CI
Just lately i have noticed that the timer is set to come on in the morning and the same at night (just before i come home from work) But last few mornings has been warm so no need to have heating on. Except when i wake the heating is on. Now the timer is always...
Quick update.. Seems repressurizing the pressure vessel has done the job. The pressure is at 1.2 and has stayed at that since i drained it etc yesterday. All seems good so far.
Thank you so much for your help.
Managed to find the pressure vessel shrader valve. Removed the cap pressed the valve inside and got no water and very little air out, just a hiss for about 2/3 seconds if that. Is this right?
Now when the heating is on the pressure reaches 2.8bar and then there is water coming out of the vent...
Right then after leaving the heating alone all night woke this morning to find the pressure was on 1.0 bar (first time for everything)
Right im going to check it all over today, You say about putting a bag on the pipe outside? Does it matter if i have had the heating on or do i need it on...
If i set the pressure to 1.0 bar, when the heating is on the digital gauge on the front instead of showing the temp, if flashes 2.8/2.9 bar. But doesnt seem to go higher than that. But it doesnt always flash.
Hi all just having a few problems with my combi boiler and hoping someone with a bit of knowledge can help me out.
To start off, my boiler keeps losing its pressure on the front digital gauge. Dropping to 0.6 bar and a red light flashes, I have to unscrew a blue bleed valve of some sort...