  1. A

    Rcd spur

    No I just tested the new cable I installed with it disconnected at both ends Thanks
  2. A

    Rcd spur

    Hi Sorry Replies not replay my iPad doing its own thing There are 2 earth terminals I will look at that Thanks
  3. A

    Rcd spur

    Hi Thanks for your replays It's a CPN SU13P rcd unit I just noticed it has surge protection built in dont know if that could be something to do with It's a passive rcd unit Thanks
  4. A

    Rcd spur

    Hi I did a insulation resistance test on my fluke 1653b multifunction tester L to E, L to N AND N to E all with readings 500+ M ohms. I also tired with the lights direct in to RCD I am a qualified eletriction I have just never had anything like this and been pulling my hair with this and the...
  5. A

    Rcd spur

    Hi I have fitted some new led outside lights I have fitted a rcd spur off the ring main and rcd trips instantly iv tested all the cable and the rcd everything is fine. I have even tried a new rcd unit and wiring the lights direct to the load side of the rcd and it still trips instantly. I then...
  6. A

    RCD with double insulated spotlights

    Thank you very much for your quick reply I know what to do now thank you again
  7. A

    RCD with double insulated spotlights

    Hi Thanks for your reply The house is not currently lived in and the power is off I am doing most of the work myself to save money but I am going to get a registered electrician to come and inspect my work before anything goes live. I was just not sure what to do with the earth I don’t...
  8. A

    RCD with double insulated spotlights

    Hi I want to fit some new Spotlights in my bathroom I have got some Zone 2 double insulated spotlights 240 volts and a 30ma RCD with a fuse but i am not sure what i should do with the Earth wire when connecting. The supply to my bathroom has earth but the spotlights don't need an earth...