    Memera 2000 40 amp b mcb

    100% and thanks for clarifying. Someone mentioned I passing 6kw max but obviously meant 6ka, which won't happen. So all good many thanks for clarifying all and good to go.
  2. M

    Memera 2000 40 amp b mcb

    Oh yes. So my proposed setup should be all ok?
  3. M

    Memera 2000 40 amp b mcb

    Yes this is the thing. I worked it all out upgrading from 6 to 10mm and a 40amp type b mcb. Then someone said the mcb has 6kw max. These kilns are 7 to 7.5kw, so what would I do?
  4. M

    Memera 2000 40 amp b mcb

    So running wire from one room with the circuit breaker/mcb board into a garage behind the plasterboard for about 10 metres. Looking at gettng one of two kilns. One is 7.5kw 230v the other reads 240v/29.13a/7kw. I have a memera 2000 board. If I'm right I concluded that a 40amp mcb type b with...
  5. M

    Memera 2000 40 amp b mcb

    Exactly so why are people saying 6kw max on the mcb? Makes no sense right and I should be ok as 10mm wire and 40a mcb should be more than enough
  6. M

    Memera 2000 40 amp b mcb

    I have a kiln, 7.6kw 230 volts. I understand that 10mm twin core wire connecting to a new 40amp b mcb should work. But googling some are saying that 6kw is the max for a memera 2000 mcb? Any ideas. Should I be ok.